Products / Armored and metal-clad cable

Armored and metal-clad cable

Type MC and Type MC-HL cable for feeders, branch circuits, control and hazardous locations, 300 V to 35 kV.

Type MC cable with the interlocked aluminum armor cut back to show the binder tape and four insulated conductors, black, red, blue and a smaller green ground, each stripped to stranded copper.
  • Construction, outside to inside
  • Interlocked aluminum armor
  • Binder tape
  • Insulated conductors
  • Grounding conductor
Voltage
300 V to 35 kV
Armor
Interlocked; welded and corrugated
Armor metal
Aluminum; galvanized steel
Conductor
Copper; aluminum

Applications

Type MC with interlocked aluminum or steel armor runs on cable tray, strut and structure without conduit. Type MC-HL, with a continuously welded and corrugated sheath and an overall jacket, is listed for Class I, Division 1 locations.

  • Feeders and branch circuits without conduit
  • Cable tray and exposed runs
  • Hazardous (classified) locations, Type MC-HL
  • Patient care spaces, Type MC (HCF)

Type MC, 600 V

TypeConstructionRatingStandard
Type MCType THHN/THWN or XHHW-2 copper conductors with insulated ground, aluminum interlocked armor600 VUL 1569
Type MC feeder cableType XHHW-2 conductors in copper or AA-8000 aluminum, 6 AWG to 750 kcmil600 VUL 1569
Type MC, PVC jacketedJacket over armor for wet locations, direct burial and concrete encasement600 VUL 1569
Type MC, steel armorGalvanized steel interlocked armor600 VUL 1569
Type MC, health care facility (HCF)Redundant grounding for patient care spaces600 VUL 1569
Type AC and AC-HCFType THHN conductors, aluminum or steel armor with bonding strip600 VUL 4

Type MC-HL

TypeConstructionRatingStandard
Type MC-HL power cableType XHHW-2 conductors, continuously welded and corrugated aluminum sheath, PVC jacket600 V; 1 kVUL 1569, 2225
Type MC-HL control cableMulti-conductor, continuously welded and corrugated aluminum sheath, PVC jacket600 VUL 1569, 2225
Type ITC-HL/PLTC instrumentation cableShielded pairs and triads, continuously welded and corrugated aluminum sheath300 VUL 2250, 13

Medium-voltage armored

TypeConstructionRatingStandard
Type MC, interlocked armor3/C Type MV-105 with ground, aluminum or steel armor, PVC jacket5 kV to 35 kVUL 1072, 1569
Type MC-HL3/C Type MV-105 with ground, continuously welded and corrugated aluminum sheath5 kV to 35 kVUL 1072, 2225

Options

Conductors2 to 4 conductors with ground; composite power and control
JacketPVC; LSZH
Put-upCoils; reels; cut lengths
Data sheetsDimensions, weights and electrical data by size, issued with the quotation