Products / Tray, control and instrumentation cable
Tray, control and instrumentation cable
Multi-conductor power, control, VFD and instrumentation cable for cable tray and exposed runs.
- Construction, outside to inside
- PVC jacket
- Insulated conductors
- Copper conductor

Applications
Type TC-ER runs in cable tray and raceway and, in industrial establishments, is permitted exposed between the tray and the equipment. Instrumentation and thermocouple extension cable is built with individual or overall shields.
- Power and control circuits in cable tray
- Motor and VFD circuits
- Process instrumentation and thermocouple circuits
- Fire alarm and power-limited circuits
Power tray cable
| Type | Construction | Rating | Standard |
|---|---|---|---|
| Type TC-ER, XHHW-2 conductors | XLPE insulation, PVC jacket, with ground | 600 V; 90 °C wet or dry | UL 1277 |
| Type TC-ER, THHN/THWN conductors | PVC insulation with nylon, PVC jacket (VNTC) | 600 V | UL 1277 |
| Type TC-ER, EPR/CPE | EPR insulation, CPE jacket | 600 V; 2 kV | UL 1277 |
| VFD cable | XLPE insulation, three symmetrical grounds, overall copper tape shield, Type TC-ER | 600 V; 1 kV; 2 kV | UL 1277 |
Control cable
| Type | Construction | Rating | Standard |
|---|---|---|---|
| Type TC control cable | Multi-conductor, 14 AWG to 10 AWG, ICEA color coded | 600 V | UL 1277; ICEA S-73-532 / NEMA WC 57 |
| Shielded control cable | Overall foil or copper tape shield | 600 V | UL 1277; ICEA S-73-532 / NEMA WC 57 |
Instrumentation and signal cable
| Type | Construction | Rating | Standard |
|---|---|---|---|
| Type PLTC/ITC, overall shield | Pairs and triads, 18 AWG and 16 AWG, foil shield with drain wire | 300 V | UL 13, 2250 |
| Type PLTC/ITC, individual and overall shield | Individually shielded pairs and triads, overall shield | 300 V | UL 13, 2250 |
| Type TC instrumentation cable | Shielded pairs and triads | 600 V | UL 1277 |
| Thermocouple extension cable | Types JX, KX, TX and EX | 300 V | ASTM E230; ANSI MC96.1; UL 13 |
| Fire alarm cable | Type FPLR and FPLP, shielded and unshielded | 300 V | UL 1424 |
Options
| Conductors | 2 to 37 conductors; 1 to 50 pairs or triads |
|---|---|
| Jacket | PVC; CPE; LSZH |
| Markings | Sunlight resistant; direct burial; exposed runs (-ER) |
| Put-up | Reels; cut lengths |
| Data sheets | Dimensions, weights and electrical data by size, issued with the quotation |